Fans and filters for air exchange for electric boards. Designed and produced in Italy; characterized by a quick snap-mounting system and a front grid to make cloth filter cleaning/replacement more rapid; motors installed on bearings; more than 40.000h reliability; polyurethane sealing gaskets.
DIMENSIONS: 325x325
IMPORTANT NOTE: Airflow Direction and IP Rating on Zanardo Ventilation Units
All panel builders are reminded that the correct installation of Zanardo ventilation units requires the airflow to be configured in extraction mode (air is drawn from inside the enclosure and pushed outwards).
Should you decide to reverse the airflow to achieve positive pressure ventilation — i.e., turning the fan inwards to blow air and pressurize the enclosure — the ventilation unit's original IP protection rating will be completely lost.
Why does this happen? The louver system and the design of the external filter are engineered to repel water and dust only when the airflow pushes outwards or under standard static conditions. Reversing the airflow direction (positive pressure ventilation) creates a vacuum on the outside that risks "sucking" moisture and particles into the enclosure, nullifying the effectiveness of the IP protection.
⚠️ Recommendation: If your application strictly requires positive pressure ventilation, we invite you to contact our technical department prior to assembly to evaluate the solutions or additional filters necessary to safeguard the enclosure's sealing.
https://www.zanardo.com/en/accessori/accessori-per-ventilazione
Material: ABS UL94-V0 prot. UVA
IP54 airextraction (with protective casing for ventilation can reach IP55https://www.zanardo.com/en/accessori/cuffia-di-protezione-per-ventilazione)
The IP rating cannot be maintained if the wall ventilation operates under positive pressure (fan blowing air inwards into the enclosure).
IK08
NEMA12
Available in the following colours:
- RAL7032 - G
- RAL7035 - W
- BLACK - B
- TRANSPARENT - C
- CHROME - S
Technical data subject to change without notice
| Code | Rated Operational voltage | Rated Operational current | Power Consumption | Noise level | Air flow (free intake) | Air flow with filter set (filter included) | Operation temperature | Weight | Volume | Technical files | Quantity | Add |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| V - ph - Hz | A | W | dB (A) | m3/h | m3/h | ℃ | Kg | |||||
| ARIA-F325.2. | Filtro di uscita/Outlet filter | -15/+55 | 0,01 | 0,8 | ||||||||
| ARIA-V325-1.2. | 230, 1~,50/60 | 0,29/0,33 | 62/75 | 59/61 | 1000 | 780/790 | -15/+55 | 2,5 | 0,02 | |||
| ARIA-V325-3.2. | 115, 1~,50/60 | 0,58/0,70 | 64/80 | 66/62 | 1000 | 780/790 | -15/+55 | 2,5 | 0,02 | |||
| ARIA-V325-2.2. | 230, 1~,50/60 | 0,20/0,22 | 55/50 | 65/70 | 800 | 624/632 | -15/55 | 2,5 | 0,02 |